Blocking Reactor

 

Blocking Reactor sometimes is also called as Detuned Filter or Low Pass Filter. The main function of this blocking reactor is to protect the capacitor unit from being exploit by the excessive level of power harmonic in the electrical network.

 

Blocking Reactor is commonly available at 6%, 7% and 13%. Other ranges like 5%, 14% and etc are available on request. However, we are only concentrate on 7%.

 

The selection for 7% Blocking Reactor against Capacitor are as per following table.

L/mH

Ith

Rated kVAR at

525V 50Hz

kVAR at

415V 50Hz

System

List Price

(MYR)

6.140

10.9

10

6.7

on request

4.094

16.4

15

10.0

on request

3.070

22.0

20

13.4

on request

2.456

27.3

25

16.7

on request

2.047

32.8

30

20.1

on request

1.535

43.7

40

26.7

on request

1.228

54.6

50

33.4

on request

1.023

65.5

60

40.1

on request

0.819

82.0

75

50.1

on request

1.722

92.8

85

56.8

on request

0.682

98.4

90

60.2

on request

0.614

109.3

100

66.9

on request

0.512

131.1

120

80.2

on request

0.409

163.9

150

100.3

on request

 

The conversion from 525V 50Hz 3-phase rated capacitor to 415V 50Hz 3-phase system with 7% Blocking Reactor are as follow.

 

Qc = [(525/415)2 * Qr] - 7%

 

Qc = kVAR at 415V 50Hz system

Qr = Rated kVAR at 525V 50Hz

 

Other sizes are available upon request.

Beside LV Blocking Reactor, we are also having 3.3kV, 6.6kV & 11kV Iron Core and Air Core Blocking Reactor, Damping Reactor, Current Limiting Reactor (Single-phase unit) and Shunt Reactor. 

 

The above are estimated prices only. Please do not hesitate to contact us for better pricing base on your desired brand, sizes and quantity.

 

Back to Products & Services main page.

 