POWER
QUALITY CATEGORY |
TYPICAL
EFFECTS AND PROBLEMS |
MEASUREMENT
METHOD |
TYPICAL
CAUSES |
TYPICAL
CONDITIONING SOLUTIONS |
Transients |
Random
equipment failures
Computer data errors |
Peak
Hold
Rise Time
Pulse Duration |
Lighting
ESD
Load switching |
Surge
arrestors
Isolation Transformers
Filters
LVC Conditioners |
Sags/Surges
Slow >100ms |
Computer
data errors
Power supply failures. |
Peak/Through
Hold
Pulse Duration |
Load
switching
Lifts
Industrial equipment
Motor starting |
Voltage
Stabilizers
Ferroresonant Transformers |
Dropouts/Surges
Fast < 30ms |
Lighting
flicker
Computer data loss
Random equipment resets/errors |
Peak/Trough
Hold
Pulse Hold |
Load
switching
Fuse clearing
Arc furnaces |
Electronic
Voltage Stabilizers
Ferroresonant Transformers
Mains Voltage Compensators |
Under/Over
Voltages |
Motor
torque reduction
Motor overheating
Motor burn out
Circuit breaker tripping
Power supply failure |
RMS
Vs Time
Statistics
Waveform
Peak/RMS |
Industrial
sites
System overload
Load shedding
Tap changing |
K-factor
Transformers
Ferroresonant Transformer
Voltage Stabilizers
Mains Voltage Compensators |
Voltage
Flicker |
Lighting
problems/flicker
Transformer noise
Computer data loss
Monitor screen wobble |
Flicker
Meter
Magnitude/Frequency
of occurrence
Modulation Frequency |
Tap
changing
Load switching
Load variations |
Electronic
Voltage Stabilizer
Ferroresonant Transformers |
Harmonic
Current
Distortion
3 Phase |
Neutral
cables overheating/fires
Transformer burn outs
High neutral to ground voltages/circulating currents |
THD
Spectrum Statistics
(3Wire/4 Wire) |
Non
linear loads
Variable speed drives
System resonance |
Ferroresonant
Transformers
Passive Filters
Active Harmonic Conditioners |
Harmonic
Current Distortion |
Transformers
overheating/fires
Monitor screen wobble |
THD
Spectrum Statistics |
Non
linear loads
Variable speed drives |
Passive
Filter Series/Parallel
Ferroresonant Transformer
Active Harmonic Conditioners |
Harmonic
Voltage Distortion |
Random
equipment resets/crashes
Clock problems
Synchronizing problems due to multiple zero crossings |
THD
Spectrum Statistics
(L-L)
(L-N)
(N-E) |
High
levels of non linear current
Variable speed drives
System resonance
High system impedance |
Electronic
Voltage Stabilizer
(Waveform correction option)
Active Harmonic Conditioner |
Interruptions
Power Failure |
Black
outs
Data loss
Network failures
Production line down time |
Duration
against time |
Fuse
fault clearing
Load shedding
Lightning (interrupters) |
Uninterruptible
Power Supplies
Back up generators |
Bad
Power Factor |
High
maximum demand
Over sized supply |
kVA/kW
kVAR |
Motor
Loads
Lighting systems |
Power
factor correction
Capacitor banks fixed/auto |